Trickle Current Heating is used to keep the
temperature of the motor
above the dew
point during times when
not in use.
Set
by a single parameter (units of amps)
Limited
to 50% FLA of motor (0 amps disables)
Wattage
calculation based upon amperage
and
motor stator resistance
Enabled automatically once motor stops and
after a 300 second
delay
Digital
input provided for customers that want
control
via hardware input for CTD operating modes
Modbus
coil provided for building automation
control
systems
Additional
benefit of providing anti-windmilling torque